PatchSiren

PatchSiren cyber security CVE debrief

CVE-2025-7545 Siemens CVE debrief

CVE-2025-7545 was published on 2025-06-10 and is described in the source corpus as a heap-based buffer overflow in GNU Binutils 2.45. Siemens’ CSAF advisory maps the CVE to specific SIMATIC S7-1500 CPU family products and notes that the attack requires local access. The source description also says the exploit has been publicly disclosed. Siemens’ documented mitigations focus on restricting access to the interactive shell of the additional GNU/Linux subsystem and only building or running trusted applications; the advisory set in the corpus states that no fix is currently available for the affected products.

Vendor
Siemens
Product
SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0)
CVSS
MEDIUM 5.3
CISA KEV
Not listed in stored evidence
Original CVE published
2025-06-10
Original CVE updated
2026-05-14
Advisory published
2025-06-10
Advisory updated
2026-05-14

Who should care

Operators, integrators, and maintenance teams responsible for the listed Siemens SIMATIC S7-1500 CPU 1518/1518F MFP variants, especially where the additional GNU/Linux subsystem is enabled or interactive shell access is available. Security teams should also care if local user accounts, engineering workstations, or trusted-build workflows could reach the affected environment.

Technical summary

The CVE description identifies a flaw in binutils/objcopy.c copy_section that can trigger a heap-based buffer overflow in GNU Binutils 2.45. The advisory context supplied by Siemens associates CVE-2025-7545 with SIMATIC S7-1500 CPU family products and indicates local attack prerequisites. The CVSS vector provided (AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L) is consistent with a local, low-complexity issue with limited confidentiality, integrity, and availability impact. The source corpus includes a reference to a patch identifier (08c3cbe5926e4d355b5cb70bbec2b1eeb40c2944), but the Siemens remediation entries in the supplied advisory still state that no fix is available for the affected products.

Defensive priority

Medium. The issue requires local access, but public disclosure and a low-privilege attack path raise urgency for environments that expose the affected subsystem or accept untrusted local content.

Recommended defensive actions

  • Restrict access to the interactive shell of the additional GNU/Linux subsystem to trusted personnel only.
  • Limit local logins, engineering access, and maintenance accounts to the minimum necessary set of users.
  • Only build and run applications from trusted sources on affected systems.
  • Review whether affected SIMATIC S7-1500 CPU models are using the additional GNU/Linux subsystem in ways that increase local exposure.
  • Monitor Siemens ProductCERT / CISA advisory updates for any future remediation guidance or fixed software.
  • Treat the issue as higher priority if untrusted local users, uploaded content, or shared service accounts exist on the system.

Evidence notes

The supplied source corpus ties the CVE to Siemens’ CSAF advisory ICSA-25-162-05 and lists affected product names for the SIMATIC S7-1500 CPU family. The CVE description supplied in the corpus is GNU Binutils-specific (copy_section in binutils/objcopy.c, heap-based buffer overflow, local attack, public exploit disclosure). Because the corpus does not provide a full vendor root-cause explanation for the Siemens products beyond the advisory mapping, the debrief keeps the technical summary bounded to the supplied evidence. The corpus also contains a remediation set that says no fix is currently available, even though the CVE description references a patch identifier; this was treated as a source-context discrepancy rather than resolved as a confirmed fixed version.

Sources and references

Verified primary and authoritative sources

  • CVE-2025-7545 CVE Program record

    Publisher, destination, and source semantics verified

    URL: https://www.cve.org/CVERecord?id=CVE-2025-7545

    CVE Program - Official CVE Program record with source-provided CVE metadata.

  • CVE-2025-7545 NVD vulnerability detail

    Publisher, destination, and source semantics verified

    URL: https://nvd.nist.gov/vuln/detail/CVE-2025-7545

    NIST National Vulnerability Database - Official NIST NVD detail page and source-specific vulnerability assessment.

Supplemental references

  • Source item URL

    Unverified legacy reference

    URL: https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2025/icsa-25-162-05.json

    cisa_csaf

  • Source reference

    Unverified legacy reference

    URL: https://cert-portal.siemens.com/productcert/csaf/ssa-082556.json

    Reference

  • Source reference

    Unverified legacy reference

    URL: https://cert-portal.siemens.com/productcert/html/ssa-082556.html

    Reference

  • Source reference

    Unverified legacy reference

    URL: https://www.cisa.gov/news-events/ics-advisories/icsa-25-162-05

    Reference

  • Source reference

    Unverified legacy reference

    URL: https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01

    Reference

  • Source reference

    Unverified legacy reference

    URL: https://www.cisa.gov/resources-tools/resources/ics-recommended-practices

    Reference

  • Source reference

    Unverified legacy reference

    URL: https://www.cisa.gov/topics/industrial-control-systems

    Reference

  • Source reference

    Unverified legacy reference

    URL: https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf

    Reference

Methodology and review provenance

AI-assisted synthesis based on stored public vulnerability evidence. System validation, approval state, and publication status do not by themselves establish human review of this revision. PatchSiren helps prioritize defensive review and does not prove exposure or remediation on any system.