CVE-2025-21862 Siemens CVE debrief
CVE-2025-21862 is a medium-severity local availability issue described in Siemens' advisory for the SIMATIC S7-1500 CPU family. The flaw is in the Linux drop_monitor path: when drop_monitor is built as a kernel module, a NET_DM_CMD_START netlink message can arrive during module loading and reach net_dm_monitor_start() before its spinlock is initialized, creating a denial-of-service risk. Siemens' advisory states that no fix was available at the time of publication and recommends limiting access to the additional GNU/Linux subsystem and only using trusted applications.
- Vendor
- Siemens
- Product
- SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0)
- CVSS
- MEDIUM 5.5
- CISA KEV
- Not listed in stored evidence
- Original CVE published
- 2025-06-10
- Original CVE updated
- 2026-05-14
- Advisory published
- 2025-06-10
- Advisory updated
- 2026-05-14
Who should care
Siemens SIMATIC S7-1500 CPU 1518-4/1518F-4 MFP operators, integrators, and maintenance teams, especially if the additional GNU/Linux subsystem is enabled or shell access is exposed to nontrusted users.
Technical summary
The supplied advisory corpus ties CVE-2025-21862 to an initialization-order problem in the Linux drop_monitor kernel component. If drop_monitor is compiled as a module, a local netlink NET_DM_CMD_START message may reach net_dm_monitor_start() while module loading is still in progress, before the associated spinlock has been initialized. The expected outcome is loss of availability rather than confidentiality or integrity impact. The Siemens CSAF applies this issue to five SIMATIC/SIPLUS S7-1500 CPU variants and notes that no fix was available in the advisory at publication time.
Defensive priority
Medium. Prioritize this if the additional GNU/Linux subsystem is present and any local shell or application-loading path is reachable, because the advisory gives no patch and the impact is availability-only but potentially disruptive.
Recommended defensive actions
- Inventory the affected SIMATIC S7-1500 CPU models listed in the advisory and confirm whether the additional GNU/Linux subsystem is enabled.
- Restrict interactive shell access to the additional GNU/Linux subsystem to trusted personnel only.
- Only build and run applications from trusted sources on the affected subsystem.
- Monitor Siemens ProductCERT and CISA updates for a future fix or revised mitigation guidance.
- Reduce unnecessary local access paths to the affected subsystem to limit exposure while no fix is available.
Evidence notes
This debrief is based only on the supplied CISA CSAF source item and the linked Siemens advisory references. The source description explicitly states the initialization-order issue, the potential for a netlink NET_DM_CMD_START message during module loading, and the uninitialized spinlock in net_dm_monitor_start(). The CISA CSAF record lists five affected Siemens product variants, a CVSS 3.1 vector of AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H, and remediation text stating that no fix was available and recommending restricted shell access and trusted-source-only application use. The supplied corpus does not list a KEV entry or a ransomware association. CVE publication date used here is 2025-06-10; later CISA republication updates in the timeline are advisory maintenance events, not the CVE issue date.
Official resources
-
CVE-2025-21862 CVE record
CVE.org
-
CVE-2025-21862 NVD detail
NVD
-
Source item URL
cisa_csaf
-
Source reference
Reference
-
Source reference
Reference
-
Source reference
Reference
-
Source reference
Reference
-
Source reference
Reference
-
Source reference
Reference
-
Source reference
Reference
CVE-2025-21862 was published on 2025-06-10 and the supplied CISA CSAF record was last updated on 2026-05-14. The source advisory states that no fix was available at publication time.