PatchSiren cyber security CVE debrief
CVE-2024-42345 Siemens CVE debrief
A session management vulnerability in Siemens SINEMA Remote Connect Server allows remote attackers to bypass multi-factor authentication (MFA) during user session establishment. The affected application fails to properly handle session establishment and invalidation, enabling MFA circumvention. Siemens has released a vendor fix in version V3.2 SP2 or later. The vulnerability carries a CVSS 3.1 score of 4.3 (Medium severity) with network attack vector, low attack complexity, and low privileges required. Published September 10, 2024, this issue affects industrial remote connectivity infrastructure and should be prioritized for patching in environments where SINEMA Remote Connect Server manages secure remote access to OT/ICS networks.
- Vendor
- Siemens
- Product
- SINEMA Remote Connect Server
- CVSS
- MEDIUM 4.3
- CISA KEV
- Not listed in stored evidence
- Original CVE published
- 2024-09-10
- Original CVE updated
- 2024-09-10
- Advisory published
- 2024-09-10
- Advisory updated
- 2024-09-10
Who should care
Organizations operating Siemens SINEMA Remote Connect Server for remote access to industrial networks, particularly those in critical infrastructure sectors relying on MFA for secure remote connectivity. Security teams responsible for OT/ICS infrastructure, network administrators managing remote access solutions, and compliance officers ensuring authentication controls meet security requirements.
Technical summary
The vulnerability exists in the session establishment and invalidation logic of SINEMA Remote Connect Server. Improper handling of user sessions allows a remote attacker with low privileges to circumvent multi-factor authentication requirements when establishing a user session. The flaw does not require user interaction and can be exploited over the network with low attack complexity. The confidentiality impact is none, integrity impact is low, and availability impact is none per the CVSS vector. Siemens has addressed this in V3.2 SP2 through improved session management controls.
Defensive priority
medium
Recommended defensive actions
- Apply vendor fix: Update SINEMA Remote Connect Server to V3.2 SP2 or later version
- Review session management configurations for proper invalidation behavior
- Implement network segmentation to limit exposure of SINEMA Remote Connect Server management interfaces
- Monitor for anomalous authentication patterns that may indicate MFA bypass attempts
- Apply defense-in-depth controls per CISA ICS recommended practices for industrial control systems
Evidence notes
Vulnerability description and remediation guidance sourced from CISA ICS advisory ICSA-24-256-01 and Siemens security advisory SSA-869574. CVSS vector confirms network-accessible attack with low complexity. Vendor fix explicitly identified as V3.2 SP2 or later.
Official resources
-
CVE-2024-42345 CVE record
CVE.org
-
CVE-2024-42345 NVD detail
NVD
-
Source item URL
cisa_csaf
-
Source reference
Reference
-
Source reference
Reference
-
Source reference
Reference
-
Source reference
Reference
-
Source reference
Reference
-
Source reference
Reference
-
Source reference
Reference
2024-09-10