PatchSiren cyber security CVE debrief
CVE-2025-53082 Samsung Electronics CVE debrief
CVE-2025-53082 is a Samsung HVAC DMS vulnerability disclosed by CISA on 2025-07-29. The issue is described as an arbitrary file deletion flaw that can let an attacker delete files from unintended locations on the filesystem. CISA lists affected Samsung HVAC DMS ranges as >=2.0.0 and <2.3.13.0, >=2.5.0.17 and <2.6.14.0, and >=2.7.0.15 and <2.9.3.5. Exploitation is restricted to specific, authorized private IP addresses, which lowers exposure but still leaves affected deployments at risk inside trusted networks. Samsung’s listed remediation is to contact a Samsung call center or installer for a software update, and the advisory says the product is intended for a separate dedicated network and should not be connected to the Internet.
- Vendor
- Samsung Electronics
- Product
- Samsung HVAC DMS
- CVSS
- HIGH 8.1
- CISA KEV
- Not listed in stored evidence
- Original CVE published
- 2025-07-29
- Original CVE updated
- 2025-07-29
- Advisory published
- 2025-07-29
- Advisory updated
- 2025-07-29
Who should care
OT and facilities teams, HVAC operators, building automation administrators, system integrators, and security teams responsible for Samsung HVAC DMS deployments—especially where the system is reachable from internal/private networks.
Technical summary
The vulnerability allows arbitrary file deletion from unintended filesystem locations in Samsung DMS (Data Management Server). In practice, that means an authorized network path can be abused to remove or damage files that the application should not be able to touch, creating integrity and availability risk. CISA’s CVSS vector is AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H (8.1 HIGH), and the advisory notes the attack path is limited to specific authorized private IP addresses.
Defensive priority
High for any environment running an affected Samsung HVAC DMS version, particularly if the system is reachable from internal networks that are not tightly segmented or if it is connected beyond the dedicated network described by the vendor.
Recommended defensive actions
- Identify all Samsung HVAC DMS instances and confirm whether they fall within one of the affected version ranges listed by CISA.
- Restrict reachability to only the specific authorized private IP addresses required for operation; remove any unnecessary internal access paths.
- Follow Samsung’s remediation guidance and contact a Samsung call center or installer to obtain and apply the software update.
- Disconnect the product from the Internet and keep it on a separate dedicated network, consistent with the vendor statement in the advisory.
- Review segmentation, firewall, and access-control rules around building management and OT networks to prevent unintended private-network exposure.
- Monitor for unexpected file deletions, service instability, or missing configuration/application files on affected systems.
- Ensure backups and recovery procedures are available and tested for HVAC/DMS environments so deleted files can be restored quickly.
Evidence notes
The source advisory describes an “Arbitary File Deletion” in Samsung DMS (Data Management Server) and says attackers can delete arbitrary files from unintended filesystem locations. It also states exploitation is restricted to specific, authorized private IP addresses. CISA published the advisory on 2025-07-29 and lists the affected Samsung HVAC DMS version ranges and Samsung’s update/disconnect guidance.
Official resources
-
CVE-2025-53082 CVE record
CVE.org
-
CVE-2025-53082 NVD detail
NVD
-
Source item URL
cisa_csaf
-
Source reference
Reference
-
Source reference
Reference
-
Source reference
Reference
-
Source reference
Reference
-
Source reference
Reference
-
Source reference
Reference
-
Source reference
Reference
CISA’s initial publication date for this advisory is 2025-07-29. The source record was published and modified the same day, and no KEV entry is listed.