PatchSiren

PatchSiren cyber security CVE debrief

CVE-2026-9634 Rockwell Automation CVE debrief

A security issue exists within the Rockwell Automation Redundancy Module Configuration Tool. The RMConfigTool.exe binary searches directories in the system path for a required DLL, and one or more of these directories may be writable by standard (non-administrator) users due to incorrect default permissions. If a local attacker places a malicious DLL in such a directory and an administrator subsequently runs the tool, the malicious DLL is loaded into the elevated process and executes with Administrator/SYSTEM privileges.

Vendor
Rockwell Automation
Product
Redundancy Module Configuration Tool
CVSS
HIGH 7.3
CISA KEV
Not listed in stored evidence
Original CVE published
2026-09-01
Original CVE updated
2026-09-01
Advisory published
2026-09-01
Advisory updated
2026-09-01

Who should care

Defenders responsible for industrial control systems, particularly those using Rockwell Automation's Redundancy Module Configuration Tool, should assess their system's exposure and take steps to mitigate the vulnerability.

Why it matters

CVE-2026-9634 allows local attackers to execute malicious DLLs with elevated privileges in Rockwell Automation's Redundancy Module Configuration Tool due to incorrect default permissions. Defenders should verify system configurations, review permissions, and update the tool to mitigate the issue.

  • Local attackers may execute malicious DLLs with elevated privileges.
  • The issue requires verification of system configurations and permissions.
  • Defenders must update the Redundancy Module Configuration Tool to version 10.01.00 or later.
  • Implementing security best practices for industrial control systems is crucial.

Technical summary

The Rockwell Automation Redundancy Module Configuration Tool has a security issue that allows local attackers to execute malicious DLLs with elevated privileges. The issue arises from the tool's search for required DLLs in directories that may be writable by standard users due to incorrect default permissions. This can occur if a local attacker places a malicious DLL in a writable directory and an administrator subsequently runs the tool, allowing the malicious DLL to be loaded into the elevated process and execute with Administrator/SYSTEM privileges. Defenders should verify system configurations, review permissions on directories in the system path, and ensure that the Redundancy Module Configuration Tool is

Defensive priority

Defenders should prioritize verifying system configurations, reviewing permissions on directories in the system path, and ensuring that the Redundancy Module Configuration Tool is updated to version 10.01.00 or later.

Recommended defensive actions

  • Verify that the Redundancy Module Configuration Tool is updated to version 10.01.00 or later.
  • Review and correct permissions on directories in the system path to prevent standard users from writing to them.
  • Implement security best practices for industrial control systems, as recommended by Rockwell Automation and CISA.
  • Review system configurations to identify potential exposure.
  • Conduct a thorough review of asset inventory for affected products.
  • Monitor relevant logs and detection systems for suspicious activity.
  • Track and document remediation efforts and exceptions.

Evidence notes

The CVE record and source item provide details on the security issue in the Rockwell Automation Redundancy Module Configuration Tool. The issue arises from the tool's search for required DLLs in directories that may be writable by standard users due to incorrect default permissions.

Sources and references

Verified primary and authoritative sources

  • CVE-2026-9634 CVE Program record

    Publisher, destination, and source semantics verified

    URL: https://www.cve.org/CVERecord?id=CVE-2026-9634

    CVE Program - Official CVE Program record with source-provided CVE metadata.

  • CVE-2026-9634 NVD vulnerability detail

    Publisher, destination, and source semantics verified

    URL: https://nvd.nist.gov/vuln/detail/CVE-2026-9634

    NIST National Vulnerability Database - Official NIST NVD detail page and source-specific vulnerability assessment.

Supplemental references

  • Rockwell Automation Redundancy Module Configuration Tool

    Unverified legacy reference

    URL: https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2026/icsa-26-244-02.json

    cisa_csaf

  • Source reference

    Unverified legacy reference

    URL: https://www.cisa.gov/news-events/ics-advisories/icsa-26-244-02

    Supplemental source

  • Source reference

    Unverified legacy reference

    URL: https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01

    Supplemental source

  • Source reference

    Unverified legacy reference

    URL: https://www.cisa.gov/resources-tools/resources/ics-recommended-practices

    Supplemental source

  • Source reference

    Unverified legacy reference

    URL: https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf

    Supplemental source

  • Source reference

    Unverified legacy reference

    URL: https://www.cisa.gov/topics/industrial-control-systems

    Supplemental source

  • Source reference

    Unverified legacy reference

    URL: https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf

    Supplemental source

  • Source reference

    Unverified legacy reference

    URL: https://www.cisa.gov/uscert/ncas/tips/ST04-014

    Supplemental source

Methodology and review provenance